The quality and properties of concrete materials directly determine every output of the IS 10262:2019 mix design procedure. Using incorrect specific gravity values is one of the most common mix design errors — changing the SG of coarse aggregate from 2.65 to 2.70 (a difference apparent to many engineers as negligible) changes the calculated CA mass by approximately 20 kg/m³ and disrupts the volume balance by nearly 0.008 m³ — enough to require a full recalculation. This page provides the reference data, selection guidance, and property verification tool needed before entering values into MixDesignCalc.

CRITICAL MATERIAL PROPERTIES IN IS 10262:2019 VOLUME BALANCE:

Absolute Volume of Each Ingredient = Mass (kg) / (SG × 1000) [m³]

Error propagation example — SG error in CA:
If CA mass = 1100 kg/m³:
At SG = 2.65: V_CA = 1100 / (2.65 × 1000) = 0.4151 m³
At SG = 2.70: V_CA = 1100 / (2.70 × 1000) = 0.4074 m³
Difference = 0.0077 m³ — this appears in FA volume (gives FA mass error ~20 kg/m³)

Always use NABL lab-tested SG values from IS 2386 Part 3 pycnometer test.
Do NOT use assumed/default SG values for formal project mix designs.

Key properties required per material type:
Cement: SG (IS 4031 Part 11) | 28d strength | Setting times
Fine Agg: SG (SSD), IS 2386 Pt 3 | Absorption % | FM (IS 2386 Pt 1) | Zone
Coarse Agg: SG (SSD), IS 2386 Pt 3 | Absorption % | Impact value | Nominal size
SCM: SG | Reactivity index | LOI (Fly Ash) | Slag activity index (GGBS)
Water: pH | TDS | Cl⁻ | SO₄²⁻ | Organic matter (IS 3025)

Material Properties Reference – Cement, Aggregate & SCM 2026

Select a material category below to browse typical IS-tested properties for each material type. Click any material card to populate the values into the material checker below.

OPC 53 Grade HPC / Structural

IS 12269:2013
SG = 3.15
  • 28d strength ≥ 53 MPa
  • C₃S: 45–65% | C₃A: <10%
  • Initial set: ≥ 30 min
  • Final set: ≤ 600 min
  • Best for M30+ and precast

OPC 43 Grade Standard

IS 8112:2013
SG = 3.14
  • 28d strength ≥ 43 MPa
  • Moderate C₃A content
  • Initial set: ≥ 30 min
  • Good for M20–M30
  • Most widely used in India

PPC – Fly Ash Blended Sustainable

IS 1489 Part 1:2015
SG = 2.97
  • FA replacement: 15–35%
  • 28d strength: 33–43 MPa
  • Lower heat of hydration
  • Slower early strength
  • Better long-term durability

PSC – Slag Cement Marine / Sulphate

IS 455:2015
SG = 2.90
  • GGBS: 25–70% (typically 50%)
  • 28d strength: 33–43 MPa
  • Excellent sulphate resistance
  • Best for marine & basements
  • Lowest heat generation

SRC – Sulphate Resisting Sulphate Soil

IS 12330:1988
SG = 3.15
  • C₃A ≤ 3.5% (IS 12330)
  • High C₄AF content
  • 28d strength ≥ 33 MPa
  • IS 456 Appendix B Class 2+
  • Not for chloride environments

OPC 33 Grade Low Grade

IS 269:2015
SG = 3.12
  • 28d strength ≥ 33 MPa
  • M10–M20 applications
  • Rarely used in 2026
  • Largely replaced by OPC 43
  • Not for M25+ structural

Crushed Granite Most Common

IS 383:2016 | IS 2386
SG = 2.65–2.70
  • SG (SSD): 2.65–2.70
  • Absorption: 0.5–1.0%
  • Impact value: <30% (good)
  • Angular shape — higher water demand
  • Best all-round aggregate

Crushed Basalt / Trap South India

IS 383:2016
SG = 2.85–2.95
  • SG (SSD): 2.85–2.95
  • Absorption: 0.3–0.8%
  • High density; heavy concrete
  • Impact value: <25% (excellent)
  • Common in Deccan plateau

Crushed Limestone Rajasthan / MP

IS 383:2016
SG = 2.55–2.65
  • SG (SSD): 2.55–2.65
  • Absorption: 0.5–2.0%
  • Check soundness (MgO)
  • Impact value: 25–35%
  • Lower SG → lower concrete density

Natural Gravel (Rounded) River Bed

IS 383:2016
SG = 2.60–2.68
  • SG (SSD): 2.60–2.68
  • Absorption: 0.3–1.0%
  • Lower water demand (rounded)
  • Weaker bond with paste
  • Use IS 10262 rounded correction

River Sand (Natural) Zone II Preferred

IS 383:2016
SG = 2.60–2.68
  • SG (SSD): 2.60–2.68
  • Absorption: 0.5–2.0%
  • FM: 2.6–3.0 (Zone II typical)
  • Rounded particles — workable
  • Scarce in many regions (2026)

M-Sand (Manufactured) Zone II Match

IS 383:2016 Cl. 4.1.2
SG = 2.62–2.70
  • SG (SSD): 2.62–2.70
  • Absorption: 1.0–2.5%
  • FM: 2.6–3.2
  • Angular — add +7 kg/m³ water
  • Check microfines <10%

Quarry Dust / Stone Dust Zone III–IV

IS 383:2016
SG = 2.55–2.65
  • SG (SSD): 2.55–2.65
  • Absorption: 1.5–3.5%
  • Fine; Zone III–IV range
  • Higher water demand
  • Use with caution for M30+

Fly Ash Class F IS 3812

IS 3812 Part 1:2003
SG = 2.15–2.35
  • SG: 2.15–2.35 (test per material)
  • LOI ≤ 5% (IS 3812)
  • Reactivity index ≥ 80% (28d)
  • Dosage: 15–35% cement
  • Ball-bearing effect; lower heat

GGBS Grade 80 / 100 IS 16714

IS 16714:2018
SG = 2.88–2.92
  • SG: 2.88–2.92
  • Activity index: ≥ 95% (28d) Grade 100
  • Dosage: 30–65%
  • Best SCM for marine exposure
  • Reduces D_cl by 3–5×

Silica Fume (Microsilica) HPC / M45+

IS 15388:2003
SG = 2.20–2.25
  • SG: 2.20–2.25
  • SiO₂ ≥ 85% (IS 15388)
  • Dosage: 5–15% cement
  • +2 kg/m³ water per 1% SF
  • Mandatory for M50+ in practice

Rice Husk Ash (RHA) Alternative

ASTM C618 / BIS draft
SG = 2.06–2.15
  • SG: 2.06–2.15
  • SiO₂ ≥ 85–95%
  • Dosage: 10–20% cement
  • Very high water demand
  • Research-stage in India 2026

Material Property Input Checker — IS 10262:2019

Enter or paste your NABL test results — the checker verifies values against IS 2386 acceptance ranges and flags inputs that may cause volume balance errors
Cement

Coarse Aggregate

Fine Aggregate

SCM (if used)

Material Property Verification Report

Complete Specific Gravity Reference Table – All Concrete Materials 2026

The following table provides typical specific gravity values for all concrete materials commonly used in Indian construction in 2026, along with the relevant test standard. Always use lab-tested SG values from NABL-accredited laboratories for formal project mix designs.

← Scroll horizontally →

Material IS Standard Typical SG Range SG for Design (use if no test) Absorption % (typical) Test Method Notes
OPC 53 GradeIS 12269:20133.10–3.173.15N/AIS 4031 Part 11 (Le Chatelier)Actual SG varies with clinker source
OPC 43 GradeIS 8112:20133.10–3.173.14N/AIS 4031 Part 11Slightly lower than OPC 53 typical
PPC (IS 1489 Pt1)IS 1489:20152.90–3.052.97N/AIS 4031 Part 11Lower SG due to FA dilution (SG~2.25)
PSC (IS 455)IS 455:20152.80–2.952.90N/AIS 4031 Part 11GGBS lowers SG significantly
SRC (IS 12330)IS 12330:19883.10–3.163.15N/AIS 4031 Part 11Similar to OPC 53 (low C₃A, high C₄AF)
Granite (crushed)IS 383:20162.63–2.722.680.3–1.0%IS 2386 Part 3 (pycnometer)Most common CA in India; SSD basis
Basalt / TrapIS 383:20162.82–2.962.900.2–0.8%IS 2386 Part 3Higher SG → heavier concrete; south India
LimestoneIS 383:20162.48–2.652.570.5–2.5%IS 2386 Part 3Wide range; test soundness (MgO content)
QuartziteIS 383:20162.60–2.682.640.3–0.8%IS 2386 Part 3Hard; low absorption; good for M40+
Natural GravelIS 383:20162.58–2.682.630.3–1.0%IS 2386 Part 3Rounded; use rounded correction in IS 10262
River Sand (natural)IS 383:20162.58–2.672.630.5–2.0%IS 2386 Part 3Most common FA; test FM and zone
Manufactured Sand (M-Sand)IS 383:20162.60–2.702.651.0–2.5%IS 2386 Part 3Add +7 kg/m³ water correction (IS 10262)
Fly Ash (IS 3812 Pt1)IS 3812:20032.10–2.402.25N/AIS 4031 Part 11 / specific gravity bottleVery low SG — large volume contribution
GGBS (IS 16714)IS 16714:20182.85–2.952.90N/AIS 4031 Part 11Close to OPC SG; small volume change
Silica Fume (IS 15388)IS 15388:20032.18–2.262.22N/AIS 4031 Part 11Ultra-fine; low SG but tiny dosage volume
WaterIS 456 Cl. 5.41.0001.000N/AFixed at 1.000 for designEven high-TDS water ≈ 1.001–1.003 SG (negligible)

Frequently Asked Questions – Material Selection 2026

Q: Which cement type should I use for M30 concrete in a coastal building?
For M30 concrete in a coastal building within 1km of the sea (Severe to Very Severe exposure): OPC 53 Grade + GGBS 40% is the 2026 best practice recommendation. OPC 53 provides the high early strength needed to maintain construction schedule; GGBS 40% dramatically reduces the chloride diffusion coefficient (by 3–5×), protecting the embedded reinforcement from sea salt corrosion over the structure's design life. Pure PPC or PSC are acceptable alternatives if OPC 53 + GGBS is not available, but the combined OPC 53 + GGBS system allows independent control of the binder proportions and is the most specifiable. Avoid OPC 33 or nominal PPC without testing for coastal applications.

Q: Should I use the SG from the cement manufacturer's test certificate or test it myself?
For formal IS 10262:2019 mix design documentation, you should use the SG from the NABL-accredited test certificate accompanying the cement delivery — either from the manufacturer's quality control or from an independent NABL lab. The manufacturer's test certificate SG is conducted per IS 4031 Part 11 and is reliable. For quick preliminary calculations, use 3.15 for OPC 53, 3.14 for OPC 43, 2.97 for PPC, and 2.90 for PSC. If the project specification requires independent material testing (common for government and infrastructure projects), test every cement lot at an independent NABL lab before use.

Q: What is the difference between OD, air-dry, SSD, and saturated specific gravity for aggregates?
IS 2386 Part 3 defines four moisture states: (1) OD (Oven Dry) — all moisture removed at 105°C; (2) Air-Dry — some surface moisture evaporated, pores still partially absorbed; (3) SSD (Saturated Surface Dry) — pores full of water, no free surface moisture — this is the reference state for IS 10262 mix design; (4) Saturated — pores full plus free water on surface. IS 10262:2019 uses SSD-basis SG and SSD-basis masses. The absorption percentage = (SSD mass − OD mass) / OD mass × 100. In practice, the SSD SG measured by IS 2386 Part 3 pycnometer method is the value to enter in MixDesignCalc. Never use OD SG (slightly higher, 0.01–0.03 difference) as it gives incorrect volume calculation.

Q: Can I use recycled coarse aggregate (RCA) from demolished concrete in a new mix design?
Recycled Coarse Aggregate (RCA) from demolished concrete is covered by IS 17452:2022 in India. RCA has significantly different properties from natural aggregate: SG typically 2.20–2.50 (lower due to attached mortar); absorption 3–10% (much higher than natural); variable quality; residual chloride and sulphate content. For IS 10262 mix design with RCA: (1) Test SG and absorption per IS 2386 Part 3 for each RCA lot — do not use granite SG defaults; (2) RCA should not exceed 25% of total coarse aggregate for structural concrete above M20; (3) Account for higher water absorption in batch water correction; (4) Structural engineer approval required for any structural use of RCA above M20.

Q: What fineness modulus of sand is ideal for concrete mix design?
IS 10262:2019 and IS 383:2016 prefer fine aggregate in Zone II (FM = 2.9–3.5) as the standard design condition. The ideal FM for most structural concrete is approximately 2.9–3.2 — coarse enough to reduce water demand and improve workability (compared with Zone III–IV fine sand), fine enough to provide adequate mortar volume for good cohesion and pumpability. FM below 2.4 (Zone IV) should not be used for M35+ concrete without special investigation. FM above 3.5 (Zone I) needs higher FA% to compensate for poor particle packing. Monitor FM weekly on site — FM variation of ±0.2 from design FM requires a proportioning adjustment (±1.5% FA per 0.1 FM change per IS 10262).